250 kW PCS — product view 1
250 kW PCS — product view 2
250 kW PCS — product view 3
250 kW PCS — product view 4
01
04

250 kW PCS

Categories:
Other
Tag:
other

Built-in isolation transformer, directly with three-phase 100%

unbalanced load;

Support multi-machine parallel connection to meet the needs of different power levels;

Frequency support; Voltage support;Inertia support;

Wide temperature operation: -25°C~55°C operating range;

Extreme environment: harsh environments such as humidity and salt spray;

Multi-control mode for free choice;

Integrate EMS for intelligent management

DataSheet
YOUR PROJECT. A CLEARER NEXT STEP.

Discuss 250 kW PCS.

Bring your site requirements to our Australian team. We will help identify the relevant model documents and configuration information.

Enquire about this product View product documents

Documents for this product.

All product documents
ENGINEERED FOR PERFORMANCE

Technical specifications

Explore the details behind the system.

Model

TPCS-250T

DC parameters

Maximum operating voltage

1000V

Minimum operating voltage

520V

Full load voltage range

550V~850V

Maximum input current

513A

On-grid AC parameters

Rated output power

250kW

Maximum output power

275kW

AC rated voltage

400V

AC rated frequency

50Hz/60Hz

Rated output current

360A

Maximum output current

396A

Maximum overload capacity

110% overload (long time) and 120% overload (1 min)

AC voltage range

85%UN~110%UN

AC frequency range

45-55Hz/55-65Hz (settable)

Harmonic distortion rate of maximum current

<3%

DC component of current

<0.5% rated output current

Power factor

-0.99 lead to 0.99 lag

Controllable range of reactive power

-100%~100%

Isolation method

Power frequency transformer

AC mode

3W+N+PE

Off-grid AC parameters

AC rated voltage

400V

AC rated frequency

50Hz/60Hz

Harmonic distortion rate of maximum voltage

<3% (linear load)

DC component of voltage

<0.5% UN (Linear balanced load)

Unbalanced load capacity

100%

Voltage change range

<3% UN

On-grid & off-grid switching mode

On-grid & off-grid switching capability

Planned off-grid

Passive off-grid switching method and switching time

Coupling switching cabinet, < 10ms

Efficiency

Maximum efficiency

97.40%

Basic Parameters

Dimensions (W×D×H)

1,216mm * 850mm * 2,054mm

Weight

1650kg

Permissible operating temperature range

-25°C-55°C (derating above 45°C)

Cooling type

Forced air cooling

Level of protection

IP20

Relative humidity

≤95% RH with no condensation

Maximum altitude

4,000m (derating above 2,000m)

Self-consumption during shutdown

<50W

Human-machine interface

Touch screen

Communication interface

RS485, Ethernet and CAN

Protocols supported

Modbus TCP, Modbus RTU